Quick answer

Choose 15, 20, 30 or 50A, select 120 or 240V, and enter a one-way length from 10 to 200 feet. The calculator estimates voltage drop at that current and identifies the smallest listed copper gauge that passes both planning checks. Separately verify the complete cord assembly, compatible connectors and equipment instructions; a gauge result does not approve a connection.

Interactive gauge check

Check conductor size and voltage drop

Circuit amperage
Circuit voltage
Voltage-drop limit
Copper conductor planning check
GaugePlanning ampacityDrop at 50 ftStatus
14 AWG15 A3.2% · 7.6 VAmpacity
12 AWG20 A2.0% · 4.8 VAmpacity
8 AWG40 A0.8% · 1.9 V✓ Passes
6 AWG55 A0.5% · 1.2 V✓ Passes
4 AWG70 A0.3% · 0.7 V✓ Passes

Smallest listed planning size

10 AWG copper1.2% drop · 237.0 V at the load

Planning estimate for copper conductors at the stated one-way length. Flexible-cord ampacity depends on the complete listed assembly, jacket, temperature rating, conductor count, and application. Verify the actual product and manufacturer instructions.

Check your connector endpoints separately with Cord Finder, then verify the complete cord assembly rating.

InputsAmps · volts · one-way feet
Drop target3% or 5% planning screen
ConductorsCopper, 14–4 AWG
Separate checkAssembly and connectors
DECISION PATHUse the evidence in the right order01STEP 1Enter current and one-waydistance02STEP 2Read both checks in eachgauge row03STEP 3Compare 25, 50 and 100feet at the same load04STEP 4Compare 10 and 12 AWG at100 and 200 feet
Follow the decision in order; a later check cannot repair a failed earlier check.

Enter current and one-way distance

Use the current you want to check, with the circuit voltage and the actual cord route. The tool offers four current values; it does not measure your load or infer current from a generator’s maximum watts. The length control is the one-way distance between generator and load, not the combined length of outgoing and returning conductors.

The estimate uses a two-conductor circuit path: voltage lost = 2 × current × one-way feet × copper resistance per foot. Percentage drop is voltage lost divided by the selected supply voltage. It does not model a shared neutral, unbalanced split-phase loads, three-phase wiring or generator regulation.

Read both checks in each gauge row

A row passes only when its stated planning ampacity covers the selected current and its estimated voltage drop is within the selected 3% or 5% limit. A row can fail one check while passing the other. Lower AWG numbers identify larger conductors.

The highlighted gauge is the smallest size in this limited table that meets those two assumptions. It is a size to investigate, not a universal flexible-cord rating. A listed generator extension cord or generator cord assembly can have a different permitted current because of its jacket, conductor count, temperature, terminals and intended use.

BEFORE YOU ACTKeep four checkpoints visibleREADAmps · volts ·one-way feetDo not infer missing data.CALCULATE3% or 5% planningscreenDo not infer missing data.VERIFYCopper, 14–4 AWGDo not infer missing data.CONFIRM2 primary referencesOpen and verify the source.
Keep equipment labels, calculations, system limits, and primary references separate.

Compare 25, 50 and 100 feet at the same load

These are calculated examples, not measurements of a purchased cord. Each row uses 30A, a 3% drop limit and the same resistance constants as the tool above. Notice that doubling the run can change the smallest passing gauge, while changing supply voltage changes the percentage drop.

Do not move the generator closer to an occupied space to make a smaller cord pass. Preserve safe outdoor placement and choose an appropriate rated assembly for the required route.

Illustrative copper planning results at 30A and a 3% drop target
SupplyOne-way lengthSmallest passing listed gaugeCalculated voltage lostCalculated drop
120V25 ft10 AWG1.50V1.25%
120V50 ft10 AWG3.00V2.50%
120V100 ft6 AWG2.37V1.98%
240V100 ft10 AWG5.99V2.50%

Compare 10 and 12 AWG at 100 and 200 feet

For a 120V, 20A two-conductor path, the calculator’s fixed copper assumptions give the results below. These are steady-state calculations using one-way cord length, not measurements or approvals of a flexible-cord product. At 100 feet, 10 AWG has less drop than 12 AWG, but neither meets the tool’s 3% target. Only 10 AWG meets a 5% comparison target. At 200 feet, neither meets either target.

Amp rating and voltage drop are separate checks. Even if a particular 12 AWG assembly is manufacturer-rated for the intended 20A load and environment, that rating does not erase its calculated 6.35V loss over this 100-foot example. Likewise, choosing a heavier gauge does not increase the ratings of its plug, connector or generator receptacle. Review the actual assembly, starting current and equipment input limits before choosing a long run.

Calculated examples at 120V and 20A using the tool’s fixed resistance values
One-way runGaugeVoltage lostDrop3% / 5% comparison
100 ft12 AWG6.35V5.29%Fails / fails
100 ft10 AWG4.00V3.33%Fails / meets
200 ft12 AWG12.70V10.59%Fails / fails
200 ft10 AWG7.99V6.66%Fails / fails

The values behind the estimate

The tool uses fixed copper resistance values and simplified planning ampacities shown here. It makes no adjustment for conductor temperature, plug contact resistance, generator voltage sag, cable reactance or starting transients. The 3% and 5% controls are comparison targets; neither is a universal approval threshold for every device or installation.

For a motor or compressor, the current during starting may be much higher than the selected operating current. Check the equipment’s starting needs separately. A steady-state calculation cannot demonstrate that a long cord will start a particular pump or air conditioner.

Fixed assumptions used by this calculator, not a listed flexible-cord ampacity chart
Copper gaugeResistance (ohms per 1,000 ft)Tool planning ampacity
14 AWG2.52515A
12 AWG1.58820A
10 AWG0.99930A
8 AWG0.628240A
6 AWG0.395155A
4 AWG0.248570A

Check the endpoints after comparing gauges

Use Cord Finder for the separate connector-compatibility check. Record the designation at the generator and at the load or inlet, then verify voltage, conductors, grounding and the complete assembly rating. A thicker cable cannot correct an incompatible generator plug.

A building connection still requires suitable transfer equipment, an approved inlet and qualified installation. This calculator does not inspect panel wiring, neutral bonding, local requirements, damaged equipment or installation quality.

Frequently asked questions

Common questions

Can watts alone determine generator cord size?

No. Connector type, voltage, current, distance, conductor count, load behavior, and product ratings also matter.

Does the calculator check generator plugs?

No. It compares copper gauges and estimated voltage drop. Use Cord Finder for the separate connector-compatibility check, then verify the complete cord assembly.

What gauge does the tool show for a 100 foot, 30A cord?

With its fixed assumptions and a 3% target, it shows 6 AWG at 120V and 10 AWG at 240V. These are planning examples, not approval of a particular cord or split-phase installation.

Does the calculator replace an electrician?

No. It cannot inspect or approve building wiring, grounding, transfer equipment or site-specific conductor requirements.

Why does distance matter?

Longer conductors add resistance and voltage drop, which can affect equipment performance and heat.

Is 10 gauge better than 12 gauge for a 100 or 200 foot generator cord?

Its lower conductor resistance reduces calculated voltage drop at the same load and distance. That alone does not approve the cord. In the tool’s 120V, 20A examples, 10 AWG drops 3.33% at 100 feet and 6.66% at 200 feet; check the complete assembly rating and equipment requirements.

Primary references

CordFind summarizes connector specifications and public safety guidance. Always follow the instructions supplied with your equipment.

  • OSHA — Using Portable Generators Safely
  • OSHA — Use of Equipment, 1910.334